G4 + F9 / H10 filter assembly
Size G4 plus F9 or H10 assemblies by complete-assembly pressure/airflow data, not sums of stage ratings.
Specifications and data conditions

Brochure p. 18 lists 610×610×347 mm assemblies. At 50 Pa: G4+F9 is 1626 m³/h and G4+H10 is 1056 m³/h.
Company material · p. 18
| Parameter | Reported field |
|---|---|
| Assembly size | 610×610×347 mm |
| G4+F9 @25 / 50 / 75 Pa | 911 / 1626 / 2351 m³/h |
| G4+H10 @25 / 50 / 75 Pa | 596 / 1056 / 1531 m³/h |
Installation and selection limits
The 50 Pa values differ by 570 m³/h. This is a duty-point difference, not a disease-control difference. F9, H10 and MERV labels are not directly interchangeable.
Manufacturer comparison
The table compares published fields. Dimensions, airflow, classes and test conditions differ; it does not establish performance/price rankings or direct interchangeability.
| Property | BSCLEAN | AAF BioShield VXL High Flow |
|---|---|---|
| Form | G4+F9/H10 two-stage assembly | AAF BioShield VXL: V-bank |
| Depth field | BSCLEAN: 347 mm | AAF BioShield VXL: nominal 12 in |
| Efficiency label | BSCLEAN: G4+F9 / G4+H10 | AAF BioShield VXL: MERV 16 / 16A |
Sources and fields to confirm
BSCLEAN values are transcribed from supplied company material, not third-party test reports. Competitor source checked: 2026-11-20。
- Supplied pig-farm air-filtration brochure · p. 18 · BSCLEAN
- AAF BioShield VXL High Flow · 2026-11-20
Confirm 5 data groups before ordering: Model efficiency report, test standard, seal drawing, target airflow, installed leakage record。
Discuss this productBuyer questions
Can the G4+H10 farm assembly deliver 1600 m³/h at 50 Pa?
Page 18 gives 1056 m³/h at 50 Pa, below 1600. Review quantity, mounting area and fan duty point.
What data should I send before ordering g4 + f9 / h10 filter assembly?
Start with 3 inputs: actual mounting dimensions, design airflow and allowed pressure drop; then confirm missing fields and model reports.
Does a filter class for g4 + f9 / h10 filter assembly guarantee a disease-free farm?
No. Verify at least 3 items: model efficiency, system seals and operating airflow. Filtration does not replace other biosecurity controls.