HEPA Gasket Direction and Frame Gaps: Seal or Resize?
Match HEPA seals and gaps to the installation.

610×610×292 mm establishes frame geometry only
BSC-WH-05 lists 610×610×292 mm. This does not specify housing tolerances, gasket compression or clamping condition. Matching the three dimensions alone does not prove there is no bypass. S1
The Camfil P example specifies 1 upstream PU gasket
Camfil Absolute CE describes -P as one PU gasket on the upstream side. This is a model marking, not the gasket direction for every HEPA. Confirm BSCLEAN seal position against the selected drawing. S2
Competitor comparison: published specifications and limits
| Comparison item | BSCLEAN BSC-WH-05 | Camfil CET14-610x610x292-P-0R |
|---|---|---|
| Frame dimensions / mm | 610×610×292 | 610×610×292 |
| Rated airflow / m³/h | 2000 | 2100 |
| Initial pressure-drop condition | Range limit listed at specified velocity; not tied to this airflow | 250 Pa at 2100 m³/h |
| Source | S1 | S2 |
This table checks published specifications, not performance or price under equal test conditions. Model ranges, duty conditions, dimension axes and classification systems differ; a single number does not establish interchangeability.
Retain 3 checks before treating a gap
Checklist: 3 items. Record frame/opening dimensions, gasket continuity and compression, and project-required leakage results. Resolve a size mismatch first. Sealant permission, type and post-repair acceptance must follow equipment and project procedures; do not substitute temporary adhesive for fit/integrity checks. Related specifications
Sources and verification date
Verified 2026-11-20. Values apply to the stated models and document editions. Supply depends on confirmed specifications. Illustrative calculations state their assumptions; undisclosed data have not been invented.
- S1 Product specification table
- S2 Camfil Absolute CE, 2025-10-24
- S3 BSCLEAN corresponding product specifications
FAQ
Should every HEPA gasket face the outlet side?
No. The Camfil -P example has one upstream PU gasket; follow the drawing.
Can I fix leakage around a 610×610×292 mm HEPA by adding sealant?
Check size, gasket/clamping and leak results, then follow repair procedures.
If the installed frame has no visible gap, can I skip HEPA leak testing?
Appearance does not replace the tests required by the project.