HEPA Filter Grades: EN 1822, ISO 29463 and GB/T 13554
Compare HEPA grades at MPPS and local leak limits.

Check the editions of all 3 standards before comparing grades
This guide compares EN 1822-1:2019, ISO 29463-1:2024 and GB/T 13554-2020. ISO identifies the 2024 publication as edition 3. China's national standards platform lists GB/T 13554-2020 as current, with an implementation date of 1 February 2021. S1 S2
The comparison concerns performance thresholds under specified test conditions. Matching thresholds do not make certificates under different standards interchangeable. State the standard, edition, class and test method in the purchase specification.
MPPS is not a fixed 0.3 µm test particle size
MPPS means Most Penetrating Particle Size. It is determined through testing and must not automatically be described as 0.3 µm. Overall efficiency describes the performance of the complete filter; local testing examines leakage at individual areas, including media and frame or seal interfaces.
For H13, the overall efficiency threshold is 99.95%, with overall penetration no greater than 0.05%. Under the reference particle-counting scan conditions, local efficiency is at least 99.75% and local penetration no greater than 0.25%. Overall and local limits are different measures. S3
EN 1822, ISO 29463 and GB/T 13554 filter class comparison
The 15 rows below compare class thresholds. Values are percentages, not fractions. Overall efficiency is a minimum and penetration a maximum. Local values refer to the reference particle-counting scan conditions. For H-group filters, alternative permitted leak-test methods can require different acceptance limits.
| Group / EN 1822-1:2019 | ISO 29463-1:2024 | GB/T 13554-2020 | Overall efficiency ≥ % | Overall penetration ≤ % | Local efficiency ≥ % | Local penetration ≤ % |
|---|---|---|---|---|---|---|
| EPA / E10 | ISO 05 E | — | 85 | 15 | — | — |
| EPA / — | ISO 10 E | — | 90 | <10, per ISO Table 2 | — | — |
| EPA / E11 | ISO 15 E | — | 95 | 5 | — | — |
| EPA / — | ISO 20 E | — | 99 | 1 | — | — |
| EPA / E12 | ISO 25 E | — | 99.5 | 0.5 | — | — |
| EPA / — | ISO 30 E | — | 99.9 | 0.1 | — | — |
| HEPA / H13 | ISO 35 H | 35 | 99.95 | 0.05 | 99.75 | 0.25 |
| HEPA / — | ISO 40 H | 40 | 99.99 | 0.01 | 99.95 | 0.05 |
| HEPA / H14 | ISO 45 H | 45 | 99.995 | 0.005 | 99.975 | 0.025 |
| ULPA / — | ISO 50 U | 50 | 99.999 | 0.001 | 99.995 | 0.005 |
| ULPA / U15 | ISO 55 U | 55 | 99.9995 | 0.0005 | 99.9975 | 0.0025 |
| ULPA / — | ISO 60 U | 60 | 99.9999 | 0.0001 | 99.9995 | 0.0005 |
| ULPA / U16 | ISO 65 U | 65 | 99.99995 | 0.00005 | 99.99975 | 0.00025 |
| ULPA / — | ISO 70 U | 70 | 99.99999 | 0.00001 | 99.9999 | 0.0001 |
| ULPA / U17 | ISO 75 U | 75 | 99.999995 | 0.000005 | 99.9999 | 0.0001 |
A dash means no corresponding class is listed in that column, or no local classification limit applies; it does not mean zero efficiency. EPA filters are not leak tested for classification purposes. GB/T 13554-2020 Table B.1 lists the local limits for classes 35 through 75. S3 S4
ISO 29463-1:2024 lists ISO 05 E at the 85% threshold and ISO 10 E at the 90% threshold. The Chinese reference illustration below uses the older comparison convention in which E10 has no ISO counterpart. Use the updated HTML table above for the 2024 edition, and verify the full agreed standard before ordering. S5

Open the Chinese reference illustration at full size
H13 versus H14: the penetration limits differ by a factor of 10
H13 permits overall penetration up to 0.05%; H14 permits up to 0.005%. The ratio is 10. This compares class limits, not measured results for any two products. It does not establish that room particle concentration will fall by a factor of 10.
For a cleanroom terminal filter or FFU, also check duty airflow, pressure drop at that airflow, actual dimensions, seal position and the installed-system acceptance method. ISO 29463-1 requires testing at the filter's nominal airflow and recording the pressure difference at that flow. An H14 label alone does not determine the pressure drop or prove compatibility with an existing H13 installation. S5
Continue with the H13 versus H14 selection guide, HEPA air filters and mini-pleat HEPA and ULPA filters.
Record 6 items in a HEPA filter purchase specification
Use this 6-item checklist to make a grade requirement traceable to an actual configuration:
- Standard number and edition, such as EN 1822-1:2019 or GB/T 13554-2020.
- Required class, overall efficiency, leak-test method and acceptance limits.
- Nominal airflow in m³/h and pressure drop in Pa at that airflow.
- Actual width, height and depth in mm, frame, mounting and seal position.
- Temperature, humidity, gas exposure and equipment material restrictions.
- Model, individual filter identification, test date and corresponding test report.
For example, class 45 has a 99.995% overall threshold. Also specify the applicable leak-test method. A media data sheet alone does not replace a test record for the complete filter.
Standard references checked on 24 November 2026
The 3 standard systems provide class and test requirements; this comparison is not evidence that a particular BSCLEAN product has obtained certification. Use the agreed edition, complete standard and model-specific test report for project acceptance.
- S1: ISO's edition and scope information for ISO 29463-1:2024.
- S2: China's official status and implementation information for GB/T 13554-2020.
- S3: EN 1822-1:2019 standard text, class groups and limits.
- S4: GB/T 13554-2020 standard text, Table B.1 local limits.
- S5: ISO 29463-1:2024 standard text, Tables 1 and 2 and nominal-flow testing.
FAQ
Which GB/T 13554 class has the same overall threshold as H13?
Class 35: 99.95%. Also verify the leak test and test conditions.
Does H14 have the same overall threshold as ISO 45 H and GB class 45?
Yes: 99.995%. State the edition and leak-test method when ordering.
Can a filter rated at 99.99% overall efficiency be specified as H14?
No. H14 requires at least 99.995% overall efficiency.
Why does a recent ISO table list ISO 05 E beside EN E10?
ISO 29463-1:2024 lists ISO 05 E at 85%; older tables can differ.
Does MPPS on a HEPA test report always mean a 0.3 µm particle?
No. MPPS is determined by testing; check the filter's test report.
Can I replace an FFU H13 filter with H14 without checking the fan?
Check duty airflow, pressure drop, dimensions and seals before replacement.
Submit selection parameters.