Filtration knowledge
HEPA Replacement: Pressure, Airflow and Integrity Records
Replace HEPA by flow, integrity and dP limits.

500 Pa is a model-specific calculation
Camfil CET14-610x 610x 292-P-0R lists 250 Pa at 2100 m³/h. The series recommends a final pressure drop of 2 times initial resistance. For this example, 250×2=500 Pa. This is not a universal HEPA replacement threshold. S4
750 Pa is the AAF page recommendation
The AAF Asia AstroCel I page specifies a recommended final resistance of 750 Pa and depths of 149 and 292 mm. That recommendation belongs to the listed family, not every HEPA model. Check the project airflow, fan capability and integrity requirements. S3
Published HEPA supplier data
| Parameter | BSCLEAN BSC-WH-05 | Camfil CET14-610x 610x 292-P-0R | AAF AstroCel I, Asia |
|---|---|---|---|
| Dimensions / mm | 610×610×292 | 610×610×292 | Family depths 149 / 292 |
| Airflow and pressure condition | 2000 m³/h; family resistance at 0.25/0.5/0.75 m/s is not assigned to that rated flow | 2100 m³/h at 250 Pa | Model duty point not listed on reviewed page |
| Final resistance basis | Not stated in source; confirm for project | 2 times initial; example 500 Pa | Page recommends 750 Pa |
| Sources | S1 | S2 | S3 |
Model coverage and operating conditions differ. The table is not a brand ranking, and a final-resistance figure cannot be transferred to another product.
Equal 610×610×292 mm dimensions still require separate records
The BSCLEAN and Camfil examples share 610×610×292 mm dimensions but list 2000 and 2100 m³/h respectively. Record the installed model, duty airflow, initial pressure drop and measuring points. Compare subsequent readings under equivalent conditions. Media or gasket problems require the project checks; pressure below 500 Pa does not prove integrity. S1 S2
Sources and verification date
Verified on 2026-11-20. Manufacturer pages and regional versions may change. Confirm the ordered model and specification.
- S1 BSCLEAN catalog, pages 23–24; model and velocity conditions.
- S2 Camfil Absolute CE; model table and final-resistance recommendation.
- S3 AAF Asia AstroCel I; specification table.
- S4 Camfil Absolute CE data sheet, 2025-10-24.
FAQ
Must every HEPA filter be replaced at 500 Pa pressure drop?
No.500 Pa is the 2×initial example for the Camfil model, not a general limit.
Are all 610×610×292 mm HEPA filters interchangeable?
No. The two examples list 2000 and 2100 m³/h. Confirm class, duty and seals.
Can the AAF750 Pa final-resistance recommendation be used for BSCLEAN?
No.750 Pa is from the AAF family page; confirm the BSCLEAN project limit.
Submit selection parameters.
Share dimensions, airflow, application and quantity for product selection and a quotation.
Get a quote