Selection guides

Air Filter Selection: Parameters and Supplier Data

Match class, airflow, dP, dimensions and seals.

BSCLEAN metal-frame panel pre-filters

Distinguish actual depths of 46 mm and 48 mm

BSCLEAN BSC-ZG4-3 is 592×592×46 mm. The Camfil 30/30 G comparison model is 592×592×48 mm: a 2 mm depth difference. Confirm the slot, gasket and clamping allowance before treating them as replacements. S1 S2

Quote pressure drop with its operating condition

The BSC-ZG4-3 G4 value is 72 Pa at 2.5 m/s. The Camfil comparison model lists 70 Pa at 3400 m³/h. The stated duty conditions differ; these two pressure figures alone do not establish which product has lower resistance. S1 S2

Pre-filter supplier comparison

Pre-filter supplier comparison
ParameterBSCLEAN BSC-ZG4-3Camfil 30/30 GAAF RedPleat
Dimensions / mm592×592×46592×592×48592×592×48 option on website
Class labelsG3 / G4G4; ePM10 50%Family: G4, M5; Coarse 70%, ePM10 50%; confirm option
Initial resistance and dutyG4: 72 Pa at 2.5 m/s70 Pa at 3400 m³/hDuty point not listed on the reviewed page
SourcesS1S2S3

This is a comparison of published specifications, not a controlled performance test. Class labels from different standards are not interchangeable solely by name.

Record 6 groups of purchasing conditions

Use these 6 groups in the inquiry:

  • Application, temperature, humidity and gases.
  • Test standard, class and reporting requirement.
  • Operating airflow per filter, in m³/h.
  • Initial resistance at that duty and the project final limit, in Pa.
  • Actual width×height×depth, in mm.
  • Frame, gasket location and retention method.

The 592×592×46 mm and 592×592×48 mm examples above are actual model dimensions, not proof of interchangeability.

Sources and verification date

Verified on 2026-11-20. Manufacturer pages and regional versions may change. Confirm the ordered model and specification.

  • S1 BSCLEAN catalog, pages 17–18; model tables.
  • S2 Camfil Singapore, 30/30 G specification table.
  • S3 AAF Europe, RedPleat specifications and BIM options.

FAQ

Why is a 592×592 mm size insufficient for a G4 filter replacement?

Depth, duty and seals also matter: the examples are 46 mm and 48 mm deep.

Can a 72 Pa G4 filter be compared directly with a 70 Pa filter?

No. Compare at the same duty; here the labels use 2.5 m/s and 3400 m³/h.

What information should an industrial air filter inquiry contain?

Send the 6 condition groups above, plus quantity and delivery location.

Submit selection parameters.

Share dimensions, airflow, application and quantity for product selection and a quotation.

Get a quote

Continue reading