Selection guides
FFU Selection: Duty Airflow, Size, Power and Supplier Data
Size FFUs by duty point, fit, power and controls.

Check the 1175×575×285 mm unit operating range
BSCLEAN BSC-UJZ-02 lists dimensions of 1175×575×285 mm, an airflow range of 700–2100 m³/h and velocity range of 0.3–0.9 m/s. These ranges do not establish that every combination occurs simultaneously. Confirm the project duty point. S1
Calculate an example using the 1170×570 mm filter
The compatible filter is listed as 1170×570×69 mm. Using only its external face gives 1.170×0.570=0.6669 m². Assuming an average face velocity of 0.45 m/s, Q=3600Av=1080.378 m³/h, approximately 1080 m³/h. This geometric example does not deduct the frame. It is not a unit rating or a cleanroom design result. S1
Published FFU supplier specifications
| Parameter | BSCLEAN BSC-UJZ-02 | Camfil HP-EC High 1132×532 | AAF AstroFan FFU–EC, Asia |
|---|---|---|---|
| Housing data / mm | 1175×575×285 | 1132×532×440 | Housing depth 295 /315; matching length and width not stated here |
| Airflow or velocity | 700–2100 m³/h;0.3–0.9 m/s | 1160 m³/h;0.5 m/s | 0.45 m/s±20%; matching airflow not listed on reviewed page |
| Supply | Single-phase 220 V,50 Hz | 200–240 V | Single-phase 230 V,50/60 Hz |
| Sources | S1 | S2 | S3 |
Dimension axes and installation definitions require confirmation. Ranges and individual duty points are not a basis for ranking power, noise or performance.
Check 220 V,230 V and 200–240 V separately
BSCLEAN lists 220 V,50 Hz; AAF Asia lists 230 V,50/60 Hz; Camfil lists 200–240 V. Confirm site voltage, frequency, motor, speed control and interface individually. The FFU product name does not establish identical electrical configurations. S1 S2 S3
Sources and verification date
Verified on 2026-11-20. Manufacturer pages and regional versions may change. Confirm the ordered model and specification.
- S1 BSCLEAN catalog, page 34; units, filters and power.
- S2 Camfil HP-EC;1132×532×440 mm High row.
- S3 AAF Asia AstroFan FFU–EC; housing and power specifications.
FAQ
Can cleanroom FFU quantity be selected from floor area alone?
No. Specify total design airflow and unit duty;700–2100 m³/h is a range.
Is 1080 m³/h from a 1170×570 mm filter at 0.45 m/s an FFU rating?
No. It is an external-face calculation; the frame has not been deducted.
Are 220 V and 230 V FFUs electrically interchangeable by name?
No. Also check 50/60 Hz, motor, wiring and controls with the supplier.
Submit selection parameters.
Share dimensions, airflow, application and quantity for product selection and a quotation.
Get a quote