Selection guides

G4 Panel Filters: Specifications to Check Before Ordering

Match G4 panel size and duty before ordering.

BSCLEAN pleated panel filters showing metal frames and filter media

Identify the G3/G4 panel filter stage

G3/G4 panel filters provide intake or AHU pre-filtration. Confirm whether the replacement serves stage 1 or another equipment-defined position. Media color does not establish the class. Do not translate the G4 label directly into an ISO ePM classification. S3

When protecting downstream pocket filters or HEPA filters, coordinate stage interfaces, airflow and pressure allowances instead of comparing purchase price alone.

592×592×46 mm versus 595×595×46 mm

The width and height differ by 3 mm. BSC-ZG4-3 lists 592×592×46 mm, while the separate specification page describes 595×595×46 mm. They are different actual dimensions, not interchangeable labels. S1

Measure the old filter, clear opening, rails and gasket contact. Use nominal inch sizes to identify a family, but manufacture and accept the replacement to the agreed millimeter drawing, tolerances and seal position.

Panel filter product showing the frame and pleated media

Beyond 46 mm depth: frame, media and seals

For a 46 mm panel filter, confirm 3 construction groups: frame, media and seal. Verify the quoted metal-frame or paper-frame construction. A wipeable frame does not establish that the media or bonding adhesive can be washed.

For paper frames, confirm moisture exposure and structural requirements. For aluminum or galvanized frames, check corrosion exposure, joints and retention. Put media, adhesive and cleaning restrictions in the specification; do not assume a fixed number of reuse cycles.

Published supplier comparison: BSCLEAN and Camfil 30/30 G

These 2 configurations share a 592×592 mm face size but differ in depth, construction and stated duty. The table does not establish equivalent performance or direct replacement.

Published supplier comparison: BSCLEAN and Camfil 30/30 G
Comparison itemBSCLEAN BSC-ZG4-3Camfil 30/30 G 1050
Actual size592×592×46 mm592×592×48 mm
Listed classificationG4ISO ePM10 50%
Initial pressure drop and condition72 Pa at 2.5 m/s face velocity70 Pa at 3400 m³/h
FrameConfirm series metal-frame option in the orderPlastic frame on the product page
Verification sourceS1S2

Depths of 46 and 48 mm are different. G4 and ePM10 50% are not a direct 1:1 equivalence. Confirm the same test basis, operating airflow and seal arrangement before substitution. Undisclosed prices, service life and performance are not compared. S3

Six inputs for a panel air filter quotation

Specify these 6 groups for pleated panel filters:

  • Actual width × height × depth in mm, housing opening and tolerances.
  • Class and test standard, with reports for cross-standard procurement.
  • Frame material, finish and retention arrangement.
  • Media and adhesive exposure limits and cleaning restrictions.
  • Operating airflow in m³/h, initial pressure-drop limit in Pa and replacement checks.
  • Quantity, destination, packaging and acceptance documents.

Review panel filter models and configurations. See the existing guides on 592 versus 595 mm fit and pre-filter washing conditions.

Sources and verification date

Verified 2026-11-25. BSCLEAN figures are existing model data; external figures come from public manufacturer documents. Different constructions and duty conditions are not an equal-condition performance test.

  • S1 BSCLEAN
  • S2 Camfil 30/30 G
  • S3 Freudenberg ISO 16890

FAQ

Can a 46 mm G4 panel filter be purchased using appearance and price alone?

No. Confirm dimensions, media, frame, seals, test basis and operating airflow.

Can a 595×595×46 mm panel filter directly replace a 592×592×46 mm filter?

Measure the opening and seal contact first; do not assume interchangeability.

Does an aluminum G4 panel filter frame mean the whole filter is washable?

No. Confirm media, adhesive and performance after the proposed cleaning method.

Can G4 and ISO ePM10 50% panel filters be treated as the same class?

No direct equivalence; require the model report for the specified test standard.

Submit selection parameters.

Share dimensions, airflow, application and quantity for product selection and a quotation.

Get a quote

Continue reading

Back to insights